Skip to main content Skip to main content

GE TJD422400L2 Q-Line Type TJD Main/Sub-Feed Molded Case Circuit Breaker, 240 VAC, 400 A, 22/10 kA Interrupt, 2 Poles, Fixed Thermal/Fixed Magnetic Trip

GE_TJD422250.jpg

Description

GE Molded Case Circuit Breaker, Type TJD Main/Sub-Feed, Series: Q-Line, 240 VAC, 400 A, 50/60 Hz Frequency, 22/10 kA Interrupt, Fixed Thermal/Fixed Magnetic Trip, 2 Pole, 1/3 ph, Pivot Handle Actuator, Load Lug Connection, Bolted-On Mounting, 10 to 50 deg C, 10-1/8 in H x 3-13/16 in D Dimensions, Plastic

The TJD line of devices include thermal magnetic molded case circuit breakers and molded case switches. The devices are complete with Cu/Al line and load lugs.

Features

  • Molded case is molded from high mechanical and high dielectric strength engineered plastic
  • Trip indication is shown by handle position midway between ON and OFF, to reset the trip mechanism, move the handle to extreme OFF, then to ON position
  • Quick make, quick break, trip free mechanism minimizes arcing during breaker operation, contacts cannot be ''teased'' into position
  • Trip free mechanism is independent of manual handle control, the breaker trips under short circuit or overload, even though the operating handle is held in ON position
  • VERIFIERâ„¢ "Twist-to-Trip" and ''Push-to-Trip'' mechanically simulates over current tripping through actuation of linkages not operated by the ON/OFF handle
  • Common trip bar assures instant disconnect of all conductors when an overload or short circuit occurs on any one conductor in the circuit or an accessory trip device operates
  • Silver alloy contacts combine the conductive properties of silver with other elements for clean, positive electrical contacting, pitting and burning are minimized for longer contact life
  • Arc chutes of heat absorbing, insulating material and metal grid plates quickly ''extinguish'' arcs
  • UL Listed lugs for copper or aluminum cable, at full frame rating, easy access and simple, straight-in wiring
  • Main or sub-feed breakers for use with 208/120 VAC 3 ph or 240 VAC 1 ph AQ panels
  • 22 kA at 120/240 VAC, 22 kA at 240 VAC, 10 kA at 250 VDC interrupt rating

Specifications

GTIN: 00783164308617

UNSPSC: 39121601

Interrupt Rating
22/10 kA
Number of Poles
2
Frequency Rating
50/60 Hz
Voltage Rating
240 VAC
Actuator Type
Pivot Handle
Dimensions
10-1/8 in H x 3-13/16 in D
Mounting Type
Bolted-On
Series
Q-Line
Connection Type
Load Lug
Phase
1/3
Material
Plastic
Amperage Rating
400 A
Temperature Rating
10 to 50 deg C
BABA Compliant
No
Type
Type TJD Main/Sub-Feed
Trip Type
Fixed Thermal/Fixed Magnetic
Sold as