Skip to main content Skip to main content

GE TED134100WL Type TED Core E Mid Tier Molded Case Circuit Breaker With CopperAluminum Line and Load Lug, 480 VAC, 100 A, 18 kA Interrupt, 3 Poles, LINon-Interchangeable Thermal Magnetic Trip

GE_TED134100WL.jpg

Description

GE Molded Case Circuit Breaker, Type TED Core E Mid Tier, 480 VAC, 100 A, 50/60 Hz Frequency, 18 kA Interrupt, E150 Frame, LI/Non-Interchangeable Thermal Magnetic Trip, 3 Pole, 3 ph, Pivot/Toggle Handle Actuator, Line/Load Lug Connection, 3 to 1 AWG Wire, Bolted-On Mounting, 10 to 50 deg C, 6-5/16 in H x 4-1/8 in W x 3-3/8 in D Dimensions, Plastic

The E150 product line consists of thermal magnetic circuit breakers, magnetic circuit breakers and molded case switches rated up to 150 A and 600 VAC. catalog numbers include the complete breaker or switch. the WL catalog number suffix indicates that the devices come with copper aluminum line and load lugs.

Features

  • Molded case is molded from high mechanical and high dielectric strength engineered plastic
  • Trip indication is shown by handle position midway between ON and off to reset the trip mechanism, move the handle to extreme off then to ON position
  • Quick-make, quick-break, trip-free mechanism minimizes arcing during breaker operation, contacts cannot be ''teased'' into position
  • Trip-free mechanism is independent of manual handle control, the breaker trips under short circuit or overload, even though the operating handle is held in on position
  • VERIFIER "twist-to-trip" and ''push-to-trip'' mechanically simulates over current tripping through actuation of linkages not operated by the on-off handle
  • Common trip bar assures instant disconnect of all conductors when an overload or short circuit occurs on any one conductor in the circuit or an accessory trip device operates
  • Silver alloy contacts combine the conductive properties of silver with other elements for clean, positive electrical contacting, pitting and burning are minimized for longer contact life
  • Arc chutes of heat absorbing, insulating material and metal grid plates quickly ''extinguish'' arcs
  • UL listed lugs for copper or aluminum cable, at full frame rating, easy access and simple, straight in wiring
  • Proven reliability
  • Provide cost effective solutions
  • Multiple types to fit in your application
  • 10 kA at 125 VDC, 10 kA at 250 VDC, 10 kA at 500 VDC, 14 kA at 600 VAC, 18 kA at 120/240 VAC, 18 kA at 240 VAC, 18 kA at 277 VAC, 18 kA at 480 VAC interrupt rating

Specifications

Type
Type TED Thermal Magnetic
Trip Type
Long Time and Instantaneous
Wire Size
3 to 3/0/1 to 3/0 AWG
Interrupt Rating
18/10 kA
Number of Poles
3
Voltage Rating
480 VAC/250 VDC
Dimensions
6-5/16 in H x 4-1/8 in W x 3-3/8 in D
Mounting Type
Bolt-On
Connection Type
Line and Load Lug
Phase
3
Amperage Rating
12 A
Temperature Rating
40 deg C
BABA Compliant
No
Sold as

Recently Viewed Products