GE TJJ436400WL Type TJJ Core J Molded Case Circuit Breaker With Copper/Aluminum Line and Load Lug, 600 VAC, 400 A, 22 kA Interrupt, 3 Poles, LI/Non-Interchangeable Thermal Magnetic Trip
GE TJJ436400WL Type TJJ Core J Molded Case Circuit Breaker With Copper/Aluminum Line and Load Lug, 600 VAC, 400 A, 22 kA Interrupt, 3 Poles, LI/Non-Interchangeable Thermal Magnetic Trip
MPN TJJ436400WL
ASPN GETJJ436400WL
UPC 783164013689
Description
Features
- Molded case is molded from high mechanical and high dielectric strength engineered plastic
- Trip indication is shown by handle position midway between ON and off to reset the trip mechanism, move the handle to extreme off then to ON position
- Quick-make, quick-break, trip-free mechanism minimizes arcing during breaker operation, contacts cannot be ''teased'' into position
- Trip-free mechanism is independent of manual handle control, the breaker trips under short circuit or overload, even though the operating handle is held in on position
- VERIFIERâ„¢ "twist-to-trip" and ''push-to-trip'' mechanically simulates over current tripping through actuation of linkages not operated by the on-off handle
- Common trip bar assures instant disconnect of all conductors when an overload or short circuit occurs on any one conductor in the circuit or an accessory trip device operates
- Silver alloy contacts combine the conductive properties of silver with other elements for clean, positive electrical contacting, pitting and burning are minimized for longer contact life
- Arc chutes of heat absorbing, insulating material and metal grid plates quickly ''extinguish'' arcs
- UL listed lugs for copper or aluminum cable, at full frame rating, easy access and simple, straight in wiring
- (1) 6 AWG to 600 kcmil, (2) 2/0 AWG to 250 kcmil copper aluminum wire range
- 20 kA at 125 VDC, 20 kA at 250 VDC, 20 kA at 500 VDC, 22 kA at 600 VAC, 30 kA at 277 VAC, 30 kA at 480 VAC, 42 kA at 120 VAC, 42 kA at 120/240 VAC, 42 kA at 240 VAC interrupt rating
Specifications
GTIN: 00783164013689
UNSPSC: 39121601
| Trip Type | LI/Non-Interchangeable Thermal Magnetic |
|---|---|
| Interrupt Rating | 22 kA |
| Number of Poles | 3 |
| Frequency Rating | 50/60 Hz |
| Voltage Rating | 600 VAC |
| Mounting Type | Bolted-On |
| Connection Type | Line/Load Lug |
| Phase | 3 |
| Material | Plastic |
| Amperage Rating | 400 A |
| Temperature Rating | 10 to 50 deg C |
| Frame | J600 |
| BABA Compliant | No |
| Weight | 14.8 lbs |
| Trip Range | 1200 to 4000 A |
| Dimensions | 10-1/8 in H x 8-1/4 in W x 3-13/16 in D |
| Actuator Type | Pivot/Toggle Handle |
| Wire Size | 6 AWG to 600 kcmil, 2/0 AWG to 250 kcmil |
| Type | Type TJJ Core J |
| Sold as |