Skip to main content Skip to main content

GE TJK636300WL Type TJK Core J Molded Case Circuit Breaker, 600 VAC, 300 A, 20/22/30/42 kA Interrupt, 3 Poles, Electronic LI/Interchangeable Thermal Magnetic Trip

IDW_IMAGE_3d1f1e25b7c29484d2a7da552aea9a19b01ca9ed3db112e5071346eec04fefa7.jpg

Description

GE Molded Case Circuit Breaker, Type TJK Core J, 600 VAC, 300 A, 50/60 Hz Frequency, 20/22/30/42 kA Interrupt, J600 Frame, Electronic LI/Interchangeable Thermal Magnetic Trip, 900 to 3000 A Trip, 3 Pole, 3 ph, Toggle Actuator, Line/Load Lug Connection, 6 AWG to 600 kcmil, 2/0 AWG to 250 kcmil Wire, Bolted-On Mounting, 10 to 50 deg C, 10-1/8 in H x 8-1/4 in W x 3-13/16 in D Dimensions, Plastic

The J600 product line consists of thermal magnetic circuit breakers, magnetic circuit breakers and molded case switches rated up to 600 A and 600 VAC. These breakers are available with either non-interchangeable trips (designated Type TJJ) or interchangeable trips (designated types TJK/THJK). Type TJJ devices ship fully assembled while types TJK/THJK ship unassembled unless specified on the order. TJK breakers are available in two frames, 400 A frame (125 to 400 A) and 600 A frame (250 to 600 A). Trip units are not interchangeable between frames. The WL catalog number suffix indicates that the devices come with Cu/Al line and load lugs.

Features

  • Molded case is molded from high mechanical and high dielectric strength engineered plastic
  • Trip indication is shown by handle position midway between ON and OFF, to reset the trip mechanism, move the handle to extreme OFF, then to ON position
  • Quick make, quick break, trip free mechanism minimizes arcing during breaker operation, contacts cannot be ''teased'' into position
  • Trip free mechanism is independent of manual handle control, the breaker trips under short circuit or overload, even though the operating handle is held in ON position
  • VERIFIERâ„¢ "Twist-to-Trip" and ''Push-to-Trip'' mechanically simulates over current tripping through actuation of linkages not operated by the ON/OFF handle
  • Common trip bar assures instant disconnect of all conductors when an overload or short circuit occurs on any one conductor in the circuit or an accessory trip device operates
  • Silver alloy contacts combine the conductive properties of silver with other elements for clean, positive electrical contacting, pitting and burning are minimized for longer contact life
  • Arc chutes of heat absorbing, insulating material and metal grid plates quickly ''extinguish'' arcs
  • UL Listed lugs for copper or aluminum cable, at full frame rating, easy access and simple, straight-in wiring
  • (1) 6 AWG to 600 kcmil, (2) 2/0 AWG to 250 kcmil wire range
  • 20 kA at 125 VDC, 20 kA at 250 VDC, 20 kA at 500 VDC, 22 kA at 600 VAC, 30 kA at 277 VAC, 30 kA at 480 VAC, 42 kA at 120 VAC, 42 kA at 120/240 VAC, 42 kA at 240 VAC interrupt rating

Specifications

GTIN: 00783164050738

UNSPSC: 39121601

Trip Type
Electronic LI/Interchangeable Thermal Magnetic
Interrupt Rating
20/22/30/42 kA
Number of Poles
3
Frequency Rating
50/60 Hz
Voltage Rating
600 VAC
Actuator Type
Toggle
Weight
0.1 lbs
Width
2.1 in
Dimensions
10-1/8 in H x 8-1/4 in W x 3-13/16 in D
Mounting Type
Bolted-On
Trip Range
900 to 3000 A
Connection Type
Line/Load Lug
Phase
3
Material
Plastic
Amperage Rating
300 A
Temperature Rating
10 to 50 deg C
Frame
J600
BABA Compliant
No
Wire Size
6 AWG to 600 kcmil, 2/0 AWG to 250 kcmil
Type
Type TJK Core J
Sold as
EACH