Siemens 14MPX32AD Heavy Duty Full Voltage Non-Reversing Non-Combination Motor Starter, 200 to 208 VAC V Coil, 3 Poles, Open Enclosure

Siemens 14MPX32AD Heavy Duty Full Voltage Non-Reversing Non-Combination Motor Starter, 200 to 208 VAC V Coil, 3 Poles, Open Enclosure
MPN 14MPX32AD
ASPN SIE14MPX32AD
UPC 754554836546
Description
Features
- Rugged industrial design
- Half sizes for cost and space savings
- Dual voltage and dual frequency coils
- Wide range of accessories
- Easy coil access
- Overload test feature
- Straight thru wiring
- Gravity drop-out
- Large silver cadmium contacts
- 3RB type solid state overload standard
- Latest technology in arc quenching to extend contactor life
- Wide variety of enclosures in all starter configurations
- Suitable for 3-wire pilot control (NO auxiliary contact included)
- NEMA controller size 6
- Standard width enclosure
Specifications
GTIN: 00754554836546
UNSPSC: 39121521
Country of Origin: United States of America (the)
| Type | Heavy Duty Full Voltage Non-Reversing |
|---|---|
| Operating Temperature | 104 deg F |
| Number of Poles | 3 |
| Frequency Rating | 60 Hz |
| Voltage Rating | 600 VAC |
| Weight | 3 lbs |
| Enclosure Type | Open |
| Motor Power | 150 hp at 200/208 VAC, 200 hp at 220/230 VAC, 400 hp at 460/480/575/600 VAC |
| Coil Voltage | 200 to 208 VAC |
| Connection Type | Box Lug/Screw Terminal |
| Phase | 3 |
| Operating Cycles | 10000000 Cycles |
| Overload Relay | Solid-State |
| BABA Compliant | No |
| Timing | 45 to 100 ms On/60 to 100 ms Off |
| Wattage | 10 W |
| Full Load Current | 160 to 630 A |
| Dimensions | 7.09 in W x 9.65 in D x 13.2 in H |
| Amperage Rating | 540 A |
| Reset Type | Automatic/Manual |
| Auxiliary Contact Rating | 10 A at 240 VAC, 2.5 A at 250 VDC |
| Sold as | EACH |