Siemens TPS3F0625X02 Type 2 Internal Surge Protective Device With Surge Counter, 480 VAC, 47 to 63 Hz, 200 kA SCCR, 3 Phase

Siemens TPS3F0625X02 Type 2 Internal Surge Protective Device With Surge Counter, 480 VAC, 47 to 63 Hz, 200 kA SCCR, 3 Phase
MPN TPS3F0625X02
ASPN SIETPS3F0625X02
UPC 804766269240
Description
Features
- Mounts internal to SB1, SB2, SB3, type RCS switchboards, type WL low voltage switchgear, TIASTAR standard 12 in bucket motor control centers and STP series busplug on SX series busway
- Type 4 SPD intended for use in type 1 applications (type 2 cUL)
- Large block, individually fused, thermally protected, 50 kA MOVs
- All UL required OCP and safety coordination included
- 100% monitoring - every MOV is monitored, including N-G
- EMI/RFI filtering - active tracking up to -50 dB from 10 kHz to 100 MHz
- 5000 hits repetitive impulse
- Monitoring - LED indicators, audible alarm with silence switch and test button and dry contacts
Specifications
UNSPSC: 39121610
Country of Origin: United States of America (the)
| Number of Wires | 3 |
|---|---|
| Frequency Rating | 47 to 63 Hz |
| Nominal Discharge Current | 20 kA |
| Short Circuit Current Rating | 200 kA |
| Peak Surge Current | 250 kA |
| Series | TPS3 |
| Phase | 3 |
| Indicator Type | LED/Audible Alarm |
| Environmental Conditions | -15 to 140 deg F Operating, 1 to 95% Non-Condensing Relative Humidity |
| Electrical Ratings | 480 VAC |
| Response Time | <0.5 ns |
| BABA Compliant | No |
| Modes of Protection | 1800 L-G/1800 L-L |
| Type | Type 2 Internal |
| Sold as | EACH |